Softstarters, Type PST/PSTB |
![]() |
![]() |
![]() |
||
PST175.......PST300 | PSTB370.......PSTB470 | PSTB570.......PSTB1050 |
PST175.......PST300 | PSTB370.......PSTB470 | PSTB570.......PSTB1050 | |||||||||||
Normal start, 400 V | kW | 90kW | 110kW | 132kW | 160kW | 200kW | 250kW | 315kW | 400kW | 450kW | 560kW | ||
Inline
connected Inside Delta connected |
kW | 160kW | 184kW | 220kW | 257kW | 355kW | 450kW | 475kW | 670kW | 780kW | 875kW | ||
Type | PST175 | PST210 | PST250 | PST300 | PSTB370 | PSTB470 | PSTB570 | PSTB720 | PSTB840 | PSTB1050 | |||
400V | ![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
|||
500V | ![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
|||
690V | ![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
|||
Rated current | le,A | 175 | 210 | 250 | 300 | 370 | 470 | 570 | 720 | 840 | 1050 | ||
Fuse Protection 400V, 65 kA | |||||||||||||
Bussmann | Type | 170M3021 | 170M3012 | 170M3013 | 170M3015 | 170M3013 | 170M3015 | 170M3015 | 170M3018 | 170M3018 | 170M3020 2) | ||
Switch Fuse | |||||||||||||
Type | OESA250R03D80 | OESA400R03D80 | ---------- | ---------- | - | --------- | OESA630R03D80 | -- | -------------- | OESA800R03D80 | 1) | 1) | |
Line Contactor | |||||||||||||
Type | A185 | A210 | A260 | A300 | AF400 | AF460 | AF580 | AF750 | - | - | |||
By - Pass Contactor | |||||||||||||
Type | A110 | A145 | A145 | A210 | Buit-in | Buit-in | Buit-in | Buit-in | Buit-in | Buit-in |
1) PSTB840 and PSTB1050 : Switch fuse not available, use fuseholder
2) PSTB1050-69-70 has 170M6019